انذار واطفاء الحرائق

 

 

 

اجهزة الانذار المبكر

  • addressable smoke detector

-operating voltage : loop  24 v(18v – 28v)

-standby  current  : <0.3mA

-(alarm current : <1.5mA(with out remote indicator) , or <3.5mA((with  remote indicator

-fire LED : red flash in poling and illuminate in alarming

 

 

 

 

  • addressable heat detector

-operating voltage : loop  24 v(18v – 28v)

-standby  current  : <0.3mA

-(alarm current : <1.5mA(with out remote indicator) , or <3.5mA((with  remote indicator

-fire LED : red flash in poling and illuminate in alarming

 

 

 

 

 

  • addressable smoke and  heat combined detector

-operating voltage : loop  24 v(pules modulation)

– ( monitoring status) operating  current  : <0.5mA , or < 1.5mA (alarm status)

-protection area :60 m2

-installation height :<8 m

 

 

 

 

  • addressable gas detector

-operating voltage : 12 – 28v

– operating  current  : 35mA@DC24V

-alarm current : 40mA@DC24V

-operating humidity : <95% , without condensation

-alarm levels : natural gas , 10% LEL (-+30%)

 

 

 

  • conventional sounder beacon

-operating voltage : 24VDC(20V – 28 V)

– operating  current  : <100mA

-power consumption : <3.2w@DC24V

-EN54-23 coverage : C-3-8/W-2.4-5

-flash color and frequency : white , 0.5 HZ

 

 

 

  • addressable manual call point

-operating voltage : signal loop  24 v(18v – 28v) , power 24VDC(20VDC – 28VDC)

-standby  current  : loop<0.8mA , power < 2mA

-action current : loop <5mA , power < 1.5mA

-output capacity : 1A@DC30V

-input mode setting : NCorNO input mode can be set by the jumper JP4

 

 

 

 

  • loop isolator

-line voltage : 16-28VDC

-standby current : <3mA

-capacity : 32 devices

-maximum voltage at which the device isolates : 8 – 11V

-maximum voltage at which the device reconnects : 1.4 – 4V

 

 

 

 

  • addressable I / O module

-operating voltage : signal loop  24 v(18v – 28v) , power 24VDC(20VDC – 28VDC)

-standby  current  : loop<0.8mA , power < 2mA

-action current : loop <5mA , power < 1.5mA

-output capacity : 1A@DC30V

-input mode setting : NCorNO input mode can be set by the jumper JP4

 

 

 

 

  • addressable repeater

-power supply : DC24V _+20%

-overall power consumption :<3W

– working temperature : -10oC- +50oC

-relative humidity : <95% (40oC , non – condensing)

 

 

 

 

  • wireless battery heat detector

-operating voltage : 3VDC

-wireless mode :433 MHz

–  (135of) fix temperature alarm  : 57oC

-rate of rise alarm : 7.1oC /5s  A&R

 

 

 

  • wireless smoke and heat detector

-operating voltage : 3VDC

-wireless mode :433 MHz

-smoke sensitivity : 0.18 – 3db /m

–  (135of) fix temperature alarm  : 57oC

-rate of rise alarm : 7.1oC /5s  A&R

 

 

 

 

  • wireless battery smoke detector

-operating voltage : 3VDC

-wireless mode :433 MHz

–  alarm current   : < 100mA

-alarm level : >85 dB/ 3m

 

 

 

 

  • addressable alarm bell

-operating voltage : 18 – 28VDC

-standby current :<3mA

–  alarm current   : < 50mA

-alarm SPL : >95 dB

-size : Dia.150 mm

 

 

 

 

  • addressable strobe sounder

-operating voltage : 18 – 28VDC

-standby current :<3mA

–  alarm current   : < 60mA

-alarm SPL : >100 dB

-flash period : 1.0 sec

 

 

 

 

  • addressable manual call point

-operating voltage : 18 – 28VDC

-working current :<4mA

–  IP rating : IP30

-green LED indicator : normal condition

-red LED indicator : alarm condition

 

 

 

 

  • conventional smoke detector

-operating voltage : 9v – 28vDC

-stand by current : <120mA

-alarm current : <20mA@24VDC

-smoke sensitivity : 0.1 – 0.15 dB /m

 

 

 

 

  • conventional heat detector

-operating voltage : 9v – 28vDC

-stand by current : <120mA

-alarm current : <20mA@24VDC

-rate of rise alarm : 7.1oC /5s  A&R 322  60oC

 

 

 

 

  • standalone heat detector

-operating voltage : 3vDC battery

-stand by current : <10mA

-alarm current : <20mA

-alarm level : 85dB /3M

 

 

 

 

  • standalone battery smoke detector

-operating voltage : 3vDC battery

-stand by current : <10mA

-alarm current : <20mA

-alarm level : 85dB /3M

 

 

 

  • battery smoke & heat detector

-operating voltage : 3vDC battery

-stand by current : <10mA

-alarm current : <20mA

-alarm level : 85dB /3M

 

 

 

 

  • standalone LPG GAS detector

-operating voltage : AC 220 V / 50 HZ / 60 HZ

-power consumption : standby <1.5w , alarm < 3.0w

-detection threshold value : LNG , 5000PPM(10%LEL)

 

 

 

 

  • conventional UV flame detector

-operating voltage : 12v – 30v DC

-standby current : <10mA

-alarm current : < 30mA

-detection range : grade l ,25m@flame

 

 

 

 

  • standalone CO gas detector

-operating voltage : 9v – 28v DC

-standby current : 120mA

-alarm current : 20mA

-detection range : >100PPM

 

 

 

 

  • conventional push station

-operating voltage : 9v – 28v DC

-alarm current : 45mA@ 24VDC

-working humidity : <93% non – condensing

-working temperature : -10oC- +50oC

 

  • conventional manual call point 

-operating voltage : 18v – 28vDC

-working current : <4mA

-IP rating : IP30

-green LED indicator : normal condition

-red LED indicator : alarm condition

 

 

  • conventional fire strobe sounder

-operating voltage : DC15V _ 30V

– operating current : 30mA

-sound level : >88dB

-flash period : <2s

-alarm sound types : 1 kind

 

 

 

  • horn strobe

-operating voltage : 12 _ 30VDC

– operating current : <60mA

-sound level : >84dB at 10 feet

-flash period : <1.0s

-alarm sound types : 3 kinds

 

 

 

  • horn strobe

-operating voltage : 12  / 24VDC

– operating current : <100mA

-sound level : >85dB at 10 feet

-flash period : <2.0s

-IP rating : IP33

 

 

 

  • horn strobe

-operating voltage : 12 / 24VDC

– operating current : <350mA

-sound level : >112 dB at 10 feet

-flash period : <2.0s

-alarm sound types :1 kinds

 

 

 

 

  • conventional sounder beacon

-operating voltage : 24VDC (20v – 28v)

– operating current : <100mA

-EN54 – 21 coverage : C – 3 – 5/W -2.4-6

-flash color and frequency : white , 0.5HZ

-light output synchronization : meta  EN54 – 23

 

 

 

  • repeater

-operating voltage : 18 – 28VDC

– communication mode : RS485

-working humidity :<93% non-condensing

-working temperature :-10oC +50oC

-size : 190*270*30mm

-GSM module : optional

 

 

 

  • horn strobe

-operating voltage : 12 / 24VDC

– operating current : <350mA

-sound level : >112 dB at 10 feet

-flash period : <2.0s

-alarm sound types :1 kinds

 

 

 

  • entrance LED indicator

-operating voltage : 2.5VDC

– operating current : <5mA

-product size : 70.5 * 36 * 38mm

-embedded hole size : length : 26.5mm / width : 55.5mm / depth : 8mm

 

 

 

  • fire bell (6 inch) 

-working voltage : 20V _ 28VDC

– working current : <60mA@ 24vDC

-sound level : >90dB

-polarized with 2 diodes

 

 

 

  • fire bell (8 inch) 

-working voltage : 20V _ 28VDC

– working current : <60mA@ 24vDC

-sound level : >100dB

-polarized with 2 diodes

 

 

 

  • infrared linear reflex beam smoke fire detector

-power supply voltage : 16v – 28v DC

-debug current <20mA

-monitoring current <12mA

-alarm current <33mA

-over all power consumption : <3W

-temperature : -10oC +50oC

-relative humidity : <95%

-protective area : max 1400 m

 

 

  • wireless manual call point

-operating voltage : 3VDC

-operating frequency :428 MHZ  to 438 MHZ

–  IP rating : IP30

-green LED indicator : normal condition

-red LED indicator : alarm condition

 

 

 

  • explosion-proof ultraviolet flame detector (UR-EXUF)

-detection range : 15m – 30m

-detection angle : 120o

-response time  : within 10 s

-protection level : IP66

-explosion-proof grade : end II C T6 Gb Ex tD A21 T 80oC

-output method : relay output (fire alarm and fault)

-reset method : power off-reset

-operating temperature : -10oC +50oC

-electrical interface : M20

-certified product : 3C , test report , explosion proof

 

 

 

 

  • explosion-proof dual infrared flame detector (UR-EXDF)

-detection range : 15m – 30m

-detection angle : 110o

-response time  : within 15 s

-protection level : IP66

-explosion-proof grade : end II C T6 Gb Ex tD A21 T 80oC

-output method : relay output (fire alarm and fault)

-reset method : power off-reset

-operating temperature : -10oC +50oC

-electrical interface : M20

-certified product : 3C , test report , explosion proof

 

 

 

  • explosion-proof ultraviolet  and infrared flame detector (UR-EXUIF)

-detection range : 40m – 60m

-detection angle : 120o

-response time  : within 10 s

-protection level : IP66 / IP67

-explosion-proof grade : end II C T6 Gb Ex tD A21 T 80oC

-output method : relay output (fire alarm and fault) current loop [0-20mA] , hart , RS-485,RS-232

-reset method : power off-reset / auto reset

-operating temperature : -10oC +50oC / -40oC +70oC

-electrical interface : 2 x G3/4 connector

-certified product : 3C , test report , explosion proof

 

 

 

  • explosion-proof combined ultraviolet  and infrared flame detector (UR-EXCUIF)

-detection range : 30m – 40m

-detection angle : 120o

-response time  : within 15 s

-protection level : IP66

-explosion-proof grade : end II C T6 Gb Ex tD A21 T 80oC

-output method : relay output (fire alarm and fault) current loop [0-20mA]

-reset method : power off-reset / auto reset

-operating temperature : -10oC +50oC / -40oC +70oC

-electrical interface : 1 x M20 x 1.5mm  ISO

-certified product : 3C , test report , explosion proof

 

 

 

  • explosion-proof three  infrared flame detector (UR-EX3IF)

-detection range : 30m – 40m

-detection angle : 110o

-response time  : within 15 s

-protection level : IP66

-explosion-proof grade : end II C T6 Gb Ex tD A21 T 80oC

-output method : relay output (fire alarm and fault) current loop [0-20mA]

-reset method : power off-reset / auto reset

-operating temperature : -10oC +50oC / -40oC +70oC

-electrical interface : 1 x M20 x 1.5mm  ISO

-certified product : 3C , test report , explosion proof

 

 

 

  • explosion-proof optical  smoke detector

-operating voltage : DC24V -+3v(polarity)

-explosion-proof mark : ExdIIct6

-monitoring current :  <60mA

-alarm current : 10 mA – 30mA

-power time : 1OS

-working humidity : < 95% non-condensing

-the outlet thread : G20

 

 

 

  • explosion-proof heat detector

-operating voltage : DC24V-+3v(polarity)

-explosion-proof mark : ExdIIct6

-monitoring current :  <60mA

-alarm current : 10 mA – 30mA

-power time : 1OS

-working humidity : < 95% non-condensing

-the outlet thread : G20

 

 

 

  • explosion-proof smoke and heat combined detector

-operating voltage : DC24V-+3v(polarity)

-explosion-proof mark : ExdIIct6

-monitoring current :  <60mA

-alarm current :  30mA

-power time : 1OS

-working humidity : < 95% non-condensing

-the outlet thread : G20

 

 

 

 

  • explosion weather proof strobe-sounder(UR-EXST)

-operating voltage : DC24V

-standby current : <650mA

-operating humidity : <95% non-condensing

-working temperature : -20oC +50oC

-sound pressure level : 80 – 90 dB

-atmosphere pressure : 80kpa – 110kpa

-size : 82mm , height : 170mm

 

 

 

  • explosion  proof manual call point(UR-EXMCP)

-operating voltage : DC24V

-standby current : 10mA

-operating humidity : <95% non-condensing

-working temperature : -20oC +50oC

-sound pressure level : N / A

-atmosphere pressure : 80kpa – 110kpa

-size : 130 *135 * 64mm

 

 

 

  • explosion  proof flash strobe(UR-EXFS)

-operating voltage : DC24V

-standby current : <50mA

-operating humidity : <95% non-condensing

-working temperature : -20oC +50oC

-sound pressure level : N / A

-atmosphere pressure : 80kpa – 110kpa

-size : 152mm , height : 165mm

 

 

 

  • water proof box

-protection level : IP67

-function : dust-proof , rain-proof

-L*W*H : 120*190*110mm

 

 

  • smoke detector water proof

-diameter : 116mm

-inner diameter : 112.5mm

-aperture : 34mm

-height : 64mm

 

 

 

  • addressable fire telephone system

– mains power : AC 220V(+10% , -15% , 50HZ)

-standby power supply : external DC24V

-bus current : <600mA

-frequency range : 300 ~ 3400HZ

-transmission attention : <5dB

-recording duration : more then 20 min

-length of bus : <1.500m

-weight : <10 kg

-dimensions : 406 x 331 x 174  mm

– working environment  temperature : 0 ~ + 50oC , RH <95%

-bus  capacity : up to 99 code addresses

-the host supports communication with at most 3 extensions of recording

-support up to query and paying 99 segments of recording

-at most 120 call messages can be recorded

-line condition : extension loop resistance (exclusive of phone resistance) <300 Ω

 

 

 

  • voice evacuation control panel 

-maximum power output : 350 watt

-speaker driving mode : constant voltage

-evacuation message up to 1 minute

-background  audio : USB2.0

-complies with EN54 part 16

 

 

 

  • centralized monitoring emergency luminaire system

emergency lighting test panel

*single loop

*maximum 500 emergency lights per loop

*up to 16 non source emergency zone input

*up to 16 testing group

 

-centralized monitoring emergency luminaire

*220VAC 50/60 HZ power supply

* 3hours  battery discharge time 48 pcs LED  lights

 

-centralized monitoring Exit sign

*220VAC 50/60 HZ power supply

*3hours  battery discharge time

*16pcs LED  lights double side

 

 

  • conventional emergency light

LED emergency light 1UV approved

*110v-127vAC 50/60 HZ , or 220V-240VAC 50/60HZ

*non-maintained

*LED 16 pcs /bar , 1/2/3/4/5 bar

*nickel-cadmium or lead – acid

 

twin lamp LED emergency light

*220VAC 50/60HZ + 10%

*5oC +40oC- RH < 92% surface with out condensation

* SMD 2835 12PCS

 

twin spot emergency light

*110v-127vAC 50/60 HZ , OR 220V-240VAC 50/60HZ

*non – maintained

*LED 6pcs/spot twin spot

*discharge duration > 3 hours

 

exit sign TUV approved

*220vAC 50 HZ  +10%-15%

*4.8V  500 MAH

*3.8V – 41V

*0.5mm2

 

 

Exit sign

*110v-120vAC or 220VAC 50 HZ

*al housing and 6mm acrylic panel 8 LED 0.5 W

*3.6V 500mm Ah Ni – Cd

>90 min*

 

  • twin lamp LED emergency light

-rated input voltage rage : 220VAC 50/60HZ -+10%

-lamp power  : 3W*2

-working environment : -5oC +40oC

-type of battery : 6v/1.2Ah

-emergency lumens : >500lm

-charging time : <24hours

-discharge  duration : >3hours

-LED type : SMD 2835 12PCS

-remote control distance : barrier – free straight line 10 meters

-dimensions : 272(length)*117(width)*117(height) mm

-executive standard : IEC EN65098-1 & EN60598-2-22

 

 

Gas extinguishing control panel

Alarm input: two alarm zones signal input, each zone can connect up to 16 detectors.
1.M valve output: control the output of electromagnetic valve.
2.Panel outputs: circuit fault output / alarm output / fire extinguishing signal output/24VDC
output other parts working condition.
3.Power output: resettable 24VDC output, 200mA current-limited protection.
4.Automatic power shift: 220VAC power and standby battery power can be switched automatically.
5.Three levels of access control (view, operation, settings).
6.Fault Monitoring: monitor panel condition of input/output/system/power/earth/fuse and so on.
7.Disable: manually disable the panel functions and zones devices.
8.Evacuation: manually activate the fire alarm devices.
9.Silence: manually silence the sounder alarm and panel buzzer.
10. Delay time setting: you can manually set the panel reset time and release delay time.
11.Panel Security protection: metal cabinet with visible glass window.
12.GSM module (optional): GSM module allows users to receive alarm information by SMS.
13.Stability: long-term aging and testing before shipment to keep the panel is stable, safe and reliable.

 

 

 

FM-200 Fire Extinguishing System

 

  • Electric Equipment Automatic Fire System

Agent: FM 200/FK-5-1-12/C02-
Cylinder: Ce Marked-
Working Pressure: 14bar-
Test Pressure: 25bar-
Working Temperature: -30″c-+60″c-

System Activated Temperature: 140°C+10°C-

 

 

 

  • packaged fire pump system

Full Assembly (Electric , Diesel and Jockey Pumps )-
Common Base-
Suitable Suction and Discharge Piping-
Includes Check Valve, Isolation Valves and Pressure Gauges-
Diesel Fuel Tank Mounting (optional ) and Battery Connection-
Suitable Pressure Tank-
Pre – Assembled Controller-

Automatically Run and Stop Jockey Pump, Electrical Motor Pump and Diesel Pump-
Automatically Charge the Battery-
Special Water Flow Path Design for High Efficiency-
Full Test with Pressure Guage and Flow Meter at Same Time-

1- water based fire products

  • 2way fire hydrant 

-“outlet size : 2 x 2.5

-“inlet size : 4

-material : cast iron

-working pressure : 15 bar

 

 

  • 3way fire hydrant 

-“outlet size :1 x 4” and 2 x 2.5

-“inlet size : 6

-material : cast iron

-working pressure : 15 bar

 

 

  • flange type landing valve

-“outlet size :  2.5

-“inlet size : 2.5

-material : brass

-nominal pressure : 1.6Mpa

 

 

  • thread type landing valve

-“outlet size :  2.5

-“inlet size : 2.5

-material : brass

-nominal pressure : 1.6Mpa

 

 

 

  • 2way breeching inlet

-“outlet size : 2 x 2.5

-“inlet size : 4

-material : cast iron

-working pressure : 10 bar

 

 

 

  • 4way breeching inlet

-“outlet size : 4 x 2.5

-“inlet size : 6

-material : cast iron

-working pressure : 10 bar

 

 

 

  • wet alarm valve

-dimensions(mm)-

– model : UR-WAV80

-nominal diameter : 80

-OD : 88.9

-A :15.88

-B : 7.93

-Ed : 84.94

-ED : 88.9

-F : 320.3

 

 

– model : UR-WAV100

-nominal diameter :100

-OD : 114.3

-A :15.88

-B : 9.53

-Ed : 110.08

-ED : 114.3

-F : 382

 

 

 

– model : UR-WAV150

-nominal diameter :150

-OD : 168.3

-A :15.88

-B : 9.53

-Ed : 163.96

-ED : 168.3

-F : 406.4

 

 

 

– model : UR-WAV200

-nominal diameter :200

-OD : 219.1

-A :19.05

-B : 9.53

-Ed : 214.4

-ED : 219.1

-F : 446

 

 

 

  • Deluge alarm valve 

-model : UR-DXAV50

-Nominal Diameter (mm) :50

-Max.working Pressure (mpa) :1.2

-Valve Height (mm) : 165

-Flange Od (mm) : 125

-Screw No& Bore Diameter (mm) : 8*18

-Install Dimension (mm) : 920*265*550

 

 

-model : UR-DAV80

-Nominal Diameter (mm) :80

-Max.working Pressure (mpa) :1.2

-Valve Height (mm) : 250

-Flange Od (mm) : 200

-Screw No& Bore Diameter (mm) : 8*18

-Install Dimension (mm) : 950*275*575

 

 

 

-model : UR-DAV100

-Nominal Diameter (mm) :100

-Max.working Pressure (mpa) :1.2

-Valve Height (mm) : 250

-Flange Od (mm) : 215

-Screw No& Bore Diameter (mm) : 8*18

-Install Dimension (mm) : 975*285*580

 

 

 

-model : UR-DAV125

-Nominal Diameter (mm) :125

-Max.working Pressure (mpa) :1.2

-Valve Height (mm) : 270

-Flange Od (mm) : 245

-Screw No& Bore Diameter (mm) : 8*18

-Install Dimension (mm) : 995*325*580

 

 

-model : UR-DAV150

-Nominal Diameter (mm) :150

-Max.working Pressure (mpa) :1.2

-Valve Height (mm) : 270

-Flange Od (mm) : 280

-Screw No& Bore Diameter (mm) : 8*18

-Install Dimension (mm) : 1020*340*580

 

 

 

-model : UR-DAV200

-Nominal Diameter (mm) :200

-Max.working Pressure (mpa) :1.2

-Valve Height (mm) : 300

-Flange Od (mm) : 335

-Screw No& Bore Diameter (mm) : 12*12

-Install Dimension (mm) : 1020*395*395

 

 

 

model : UR-DAV250

-Nominal Diameter (mm) :250

-Max.working Pressure (mpa) :1.2

-Valve Height (mm) : 450

-Flange Od (mm) : 400

-Screw No& Bore Diameter (mm) : 12*26

-Install Dimension (mm) : 1185*460*598

 

 

  • pre-action alarm valve 

-model : UR-PAV100

-Nominal Diameter (mm) :100

-nominal working Pressure (mpa) :1.2 ~1.6

-body Height (mm) : 250

-Flange outer diameter (mm) : 220

-water pressure reduced : <0.07

-drive time (s) : 15

 

 

 

-model : UR-PAV150

-Nominal Diameter (mm) :150

-nominal working Pressure (mpa) :1.2 ~1.6

-body Height (mm) : 270

-Flange outer diameter (mm) : 265

-water pressure reduced : <0.07

-drive time (s) : 15

 

 

 

-model : UR-PAV200

-Nominal Diameter (mm) :200

-nominal working Pressure (mpa) :1.2 ~1.6

-body Height (mm) : 370

-Flange outer diameter (mm) : 340

-water pressure reduced : <0.07

-drive time (s) : 15

 

 

 

  • foam fire extinguishing system

( horizontal and vertical)

-Working Pressure Range : 0.6~1.2MPa

-Pressure Drop : 0.2MPa

– Test Pressure / Intensity: 1.5MPa , Seal : 1.32MPa

-Tank Capacity : 500~10000L

-Size of Proportioner : DN80~DN250

-Flow Rate : 4~360L/S

-Mixing Ratio : 3% or 6%

 

 

 

  • hose rack with cabinet assembly

 

-Swing-out L-shaped Arm
-Pin Type Rack Red Enamel Steel
-40mmx30m (1.5″x100″) Collapsable Hose
-Rocker Type 40 mm (1.5″) Coupling
-40mm (1.5″) Plastic Fog Type Nozzle
-40mm (1.5″) Cast Brass Angle Valve
-Cabinet is Fabricated of 0.8mm thickness carbon steel sheets
-Ventilation louvers

 

 

 

  • hose real with cabinet assembly

-Steel construction reel drum powder coated with Swivel Inlet
-38×25mm (1.5″x1 “)Cast Brass Angle Valve
-25mmx30m Length Non-Collapsable PVC Rubber Hose
-25mm(1” )Plastic Handline nozzle
-L-Shaped swing arm fixed to the cabinet
-Cabinet is Fabricated of 0.8mm thickness carbon steel sheets

 

-order information-

  • model number  : UR-FH201
  • description : fire hose rack
  • “dimensions :28″*20″*4

 

 

  • model number  : UR-FH202
  •  description :  hose rack cabinet
  • “dimensions :31.5″*30″*8

 

  • model number  : UR-FH203
  • description : fire hose reel
  • “dimensions :24″*29″*7.8

 

  • model number  : UR-FH204
  • description :  hose reel cabinet
  • “dimensions :31.5″*30″*12

 

 

 

  • heat detector tester

-Heating Element :220V/100W or 110V/100W
– Length 1.75meter x Dia.32mm Light weight Aluminum Pole
– Cable Length 30meter
– Aluminum case with lock

 

 

  • smoke detector test applicator

-Length 1.6 meter x Dia.32mm
– Light Weight Aluminum pole
– Triggering mechanism
– Aluminum case with lock

 

 

 

  • glass bulb type fire sprinkler

-type : pendent

-Material : Brass or zinc alloy

-Normal diameter (mm) :DN15 or DN20″

-Connecting thread (inch) :R1/2″ ‘ or R3/4

-Response element : Glass bulb

-Operating Temperature : 57°C/68 °C /79 °C/93 °C/141 °C/181 °C

-Response type : Standard response or Quick response

-K factor : 80(5.6 @ US) or 115 (8.0 @ US)

-Working pressure : 0.1 MPa – 1.2 Mpa(1 bar – 12 bar)

-Seal material : Teflon (PTFE) plated metal O-ring, or rubber O-rin